XL2; 800004FF task error in the Order display-field (HO) command
A customer running 4.106.0 reported an 800004FF task error. The 800004FF error indicates a task stayed in an infinite loop and did not give up CPU time for lower-priority tasks to run for a lengthy period.
The stack dump showed the UART task in the host command that selects which Order fields are shown on the status display - the "HO" command (Uart_Cmd_HO). That command parses a list of field numbers out of the message. The parsing loop only counted a field - and so only advanced toward its field-count limit - when it decoded a valid, non-zero field number. A field value of zero, which is a legitimate value meaning "field not set," was skipped without advancing the count.
That left the loop with only one remaining way to end: the message index reaching the message length. Get_String_From_UartMsg returns the index unchanged when the message length is outside its valid range, so under that condition the index stops advancing. With a zero/unset field and a non-advancing index, the loop had no way to terminate and held the UART task on the processor until the watchdog fired.
The loop has been changed to advance its position counter on every pass, not only on valid fields. The counter now tracks message position (zero still means "field not set"), which limits the loop to the maximum number of order edit fields regardless of message contents, so it can no longer spin. The loop's limit test was also corrected (<= to <) so it can no longer write one entry past the end of the field array.
| Model | Version | Released |
|---|---|---|
| XL2OL | 5.110.1 | 10/15/2026 |
| XL2OL | 5.110.1 | 10/15/2026 |
| XL220CL | 5.111.0 | 10/21/2026 |
| XL220OL | 5.111.0 | 10/21/2026 |
| XL2CL | 4.110.1 | 10/15/2026 |
| XL2OL | 4.110.1 | 10/15/2026 |
| XL220CL | 4.111.0 | 10/21/2026 |
| XL220OL | 4.111.0 | 10/21/2026 |