Problem
During the Die Accelerator Test, tripping an input monitored by the hole interrupt - the home sensor, for example - caused a momentary jump in the reported line velocity. The die accelerator tracked the jump, producing a step in the commanded and actual die motion. Machines running an actual encoder were not affected.
Cause
The simulated line encoder has no position of its own between advances. It produces counts only when the software reads it, and each read advances it by one step. The design assumes the 1 millisecond periodic sample is the only reader, so one read equals one millisecond of simulated travel.
The hole interrupt also read the encoder, on every edge of any monitored input. Before the 12-bit encoder changes this was harmless, because the simulated read did not update the shared encoder counter; the extra counts stayed local to the interrupt and the periodic sample never saw them.
The 12-bit encoder changes made the simulated read update the shared counter. That was required - without it the simulation produced no motion at all - but as a side effect each extra read deposited a step into the counter. The next periodic sample then reported two steps of travel for one millisecond of elapsed time, which the velocity calculation interpreted as approximately double the line speed.
Change
Reads performed for an event - hole detect and die encoder offset - now obtain the current count without advancing the encoder source. Periodic sampling for velocity and loop control is unchanged.
Actual encoders are unaffected. Reading a hardware counter does not create counts, so an event read still takes a fresh reading and returns the position at the moment of the event.