XL2CL
5.112.2
11/11/2026
SCN: 5441 — XL2; EtherCAT WKC errors while EC Diagnostic Screen open.

Resolved intermittent EtherCAT communication errors (working-counter faults) that could occur while the EtherCAT drive diagnostic screen was displayed.

While the diagnostic screen is open, the controller continuously gathers status information from the drives. These diagnostic messages are large and share the EtherCAT network with the regular cyclic position and status updates. Under this load, a diagnostic message could sit in the controller's receive buffer ahead of a drive's regular update, and because the controller checked for its own update one message at a time and then waited, it could fail to detect that update within the allowed time and report a communication fault.

The controller now reads all available network messages together before waiting, so a drive's regular update is detected immediately even when diagnostic data is present. In addition, the time allowed to receive each update is now calculated automatically from the number of drives and the size of their messages, so it stays correct if drives are added or the drive configuration changes.

SCN: 5442 — XL2; EC Support for CtrlX with -EX option.

EtherCAT Support for Drives with an Engineering Connection (lets the XL200 run Bosch Rexroth ctrlX drives ordered with the -EX option)

The XL200 closed-loop controller can now run EtherCAT servo drives that put an extra "engineering" connection on the network alongside the drive itself - for example Bosch Rexroth ctrlX drives ordered with the "-EX" Extended Engineering option, which always add a second connection that cannot be turned off. Until now the controller counted that extra connection as if it were a missing or unexpected drive, so it refused to start and cycled a start-up error indefinitely - the machine never ran.

The controller now recognizes the engineering connection, leaves it alone as a harmless pass-through on the network, and starts and runs the real drives normally. This adds to the controller's existing EtherCAT drive support (ctrlX, IndraDrive and Mitsubishi).

Scope not yet covered, by design: the controller allows at most one such engineering connection on the network. Two of them, or any device it cannot identify, still stops start-up on purpose rather than guessing.

SCN: 5444 — XL2; EtherCAT timing improvement

Improved timing while the EtherCAT drive diagnostic screen is displayed. The diagnostic information passed from the motion coprocessor to the main processor now uses a direct memory transfer instead of a processor-driven copy. The previous method held the processor for the duration of each transfer, which could delay time-critical network handling. The direct transfer releases the processor while the copy takes place, improving timing margins when diagnostics are shown.

SCN: 5445 — XL2; EtherCAT timing for different Indradrive types, MPB and MPE

The controller now places its command-send and feedback-read timing to match each IndraDrive's control type. Different control types run their internal position loop on different schedules, so the period during which a drive can be safely written and read differs by type. The controller reads the control type from the drive and positions its data exchange inside that drive's valid period. If drives that sample at different instants are mixed on one network, the controller reports a warning, since their motion cannot be fully coordinated.

Technical: the position-loop cycle is taken from the drive's firmware type - MPE (Economy) = 1 ms, MPB/MPM (Basic) = 500 us, MPC (Advanced) = 250 us. Using the cycle start (Sync0) as the reference, the input-latch offset t1 = one position-loop cycle when the loop runs faster than the bus, or 0 when the loop equals the bus; the actual-value protection time t2 = one-half of the position-loop cycle. The exchange window opens at Sync0 + t1 + t2 and closes at the next Sync0. On a 1 ms bus this gives MPE (t1 = 0, t2 = 500 us) a window of 500-1000 us, and MPB (t1 = 500 us, t2 = 250 us) a window of 750-1000 us. The drive's input-latch sync pulse is programmed to fire at t1 after Sync0, matching where the drive latches its inputs; the exchange window then opens t2 later, after the drive's actual-value protection time.

SCN: 5446 — XL2; EtherCAT procedure command reliability change.

Improved the reliability of EtherCAT drive procedure commands, such as clearing a drive's class-1 diagnostics or setting an absolute position. These commands start an operation on the drive and then terminate it, with the controller waiting for the drive to acknowledge each step. The controller previously allowed too little time for the acknowledgment, so on some drives the response arrived after the wait had already expired — the command appeared to fail, and the terminate step could be reported as unacknowledged even though the drive had accepted it, occasionally leaving the procedure active on the drive. The controller now allows the drive its full normal response time for both starting and terminating a procedure command, so the command completes and is confirmed reliably.