5445
XL2; EtherCAT timing for different Indradrive types, MPB and MPE
XL200

The controller now places its command-send and feedback-read timing to match each IndraDrive's control type. Different control types run their internal position loop on different schedules, so the period during which a drive can be safely written and read differs by type. The controller reads the control type from the drive and positions its data exchange inside that drive's valid period. If drives that sample at different instants are mixed on one network, the controller reports a warning, since their motion cannot be fully coordinated.

Technical: the position-loop cycle is taken from the drive's firmware type - MPE (Economy) = 1 ms, MPB/MPM (Basic) = 500 us, MPC (Advanced) = 250 us. Using the cycle start (Sync0) as the reference, the input-latch offset t1 = one position-loop cycle when the loop runs faster than the bus, or 0 when the loop equals the bus; the actual-value protection time t2 = one-half of the position-loop cycle. The exchange window opens at Sync0 + t1 + t2 and closes at the next Sync0. On a 1 ms bus this gives MPE (t1 = 0, t2 = 500 us) a window of 500-1000 us, and MPB (t1 = 500 us, t2 = 250 us) a window of 750-1000 us. The drive's input-latch sync pulse is programmed to fire at t1 after Sync0, matching where the drive latches its inputs; the exchange window then opens t2 later, after the drive's actual-value protection time.

Model Version Released
XL2CL 5.112.2 11/11/2026
XL2OL 5.113.0 11/18/2026
XL220CL 5.113.0 11/18/2026
XL220OL 5.113.0 11/18/2026