SCN: 5441 — XL2; EtherCAT WKC errors while EC Diagnostic Screen open.

Resolved intermittent EtherCAT communication errors (working-counter faults) that could occur while the EtherCAT drive diagnostic screen was displayed.

While the diagnostic screen is open, the controller continuously gathers status information from the drives. These diagnostic messages are large and share the EtherCAT network with the regular cyclic position and status updates. Under this load, a diagnostic message could sit in the controller's receive buffer ahead of a drive's regular update, and because the controller checked for its own update one message at a time and then waited, it could fail to detect that update within the allowed time and report a communication fault.

The controller now reads all available network messages together before waiting, so a drive's regular update is detected immediately even when diagnostic data is present. In addition, the time allowed to receive each update is now calculated automatically from the number of drives and the size of their messages, so it stays correct if drives are added or the drive configuration changes.

SCN: 5442 — XL2; EC Support for CtrlX with -EX option.

EtherCAT Support for Drives with an Engineering Connection (lets the XL200 run Bosch Rexroth ctrlX drives ordered with the -EX option)

The XL200 closed-loop controller can now run EtherCAT servo drives that put an extra "engineering" connection on the network alongside the drive itself - for example Bosch Rexroth ctrlX drives ordered with the "-EX" Extended Engineering option, which always add a second connection that cannot be turned off. Until now the controller counted that extra connection as if it were a missing or unexpected drive, so it refused to start and cycled a start-up error indefinitely - the machine never ran.

The controller now recognizes the engineering connection, leaves it alone as a harmless pass-through on the network, and starts and runs the real drives normally. This adds to the controller's existing EtherCAT drive support (ctrlX, IndraDrive and Mitsubishi).

Scope not yet covered, by design: the controller allows at most one such engineering connection on the network. Two of them, or any device it cannot identify, still stops start-up on purpose rather than guessing.

SCN: 5444 — XL2; EtherCAT timing improvement

Improved timing while the EtherCAT drive diagnostic screen is displayed. The diagnostic information passed from the motion coprocessor to the main processor now uses a direct memory transfer instead of a processor-driven copy. The previous method held the processor for the duration of each transfer, which could delay time-critical network handling. The direct transfer releases the processor while the copy takes place, improving timing margins when diagnostics are shown.

SCN: 5445 — XL2; EtherCAT timing for different Indradrive types, MPB and MPE

The controller now places its command-send and feedback-read timing to match each IndraDrive's control type. Different control types run their internal position loop on different schedules, so the period during which a drive can be safely written and read differs by type. The controller reads the control type from the drive and positions its data exchange inside that drive's valid period. If drives that sample at different instants are mixed on one network, the controller reports a warning, since their motion cannot be fully coordinated.

Technical: the position-loop cycle is taken from the drive's firmware type - MPE (Economy) = 1 ms, MPB/MPM (Basic) = 500 us, MPC (Advanced) = 250 us. Using the cycle start (Sync0) as the reference, the input-latch offset t1 = one position-loop cycle when the loop runs faster than the bus, or 0 when the loop equals the bus; the actual-value protection time t2 = one-half of the position-loop cycle. The exchange window opens at Sync0 + t1 + t2 and closes at the next Sync0. On a 1 ms bus this gives MPE (t1 = 0, t2 = 500 us) a window of 500-1000 us, and MPB (t1 = 500 us, t2 = 250 us) a window of 750-1000 us. The drive's input-latch sync pulse is programmed to fire at t1 after Sync0, matching where the drive latches its inputs; the exchange window then opens t2 later, after the drive's actual-value protection time.

SCN: 5446 — XL2; EtherCAT procedure command reliability change.

Improved the reliability of EtherCAT drive procedure commands, such as clearing a drive's class-1 diagnostics or setting an absolute position. These commands start an operation on the drive and then terminate it, with the controller waiting for the drive to acknowledge each step. The controller previously allowed too little time for the acknowledgment, so on some drives the response arrived after the wait had already expired — the command appeared to fail, and the terminate step could be reported as unacknowledged even though the drive had accepted it, occasionally leaving the procedure active on the drive. The controller now allows the drive its full normal response time for both starting and terminating a procedure command, so the command completes and is confirmed reliably.

SCN: 5447 — XL2; Add more help to Memory Below % error messages

The Memory Below % error messages have been modified to ecourage customers to check their Eclipse Connection or call AMS Controls before memory corruption occurs. This may encourage customers to stop ignoring these messages before blue screens, which are more difficult to diagnose, occur.

SCN: 5450 — XL2; EtherCAT Jitter improvement

Improved the steadiness of EtherCAT motion timing while the drive diagnostic screen is displayed. With the diagnostic screen open, the controller reads diagnostic information from the drive over a background message channel. On a drive with a large message size, one of these background messages could briefly occupy the network just ahead of the time-critical motion frame and nudge its timing. The controller now paces the large background messages so that at most one is sent per control cycle, and only after that cycle's motion frame has already gone out. The motion frame is therefore sent first and on schedule, keeping its timing steady while diagnostics are in use. Small background messages are left unpaced, so diagnostics stay responsive.

SCN: 5452 — XL; Encoder Simulation Spikes and ISR protection.

PROBLEM

Running a Die Accelerator Test, the simulated material velocity showed sudden spikes, with the die correctly chasing them. This affects the Die Accelerator Test only. The encoder simulation is the only encoder source that behaves this way, and a real encoder, a SERCOS drive and an EtherCAT drive were all confirmed on hardware to be unaffected.

Separately, while investigating that, a number of values shared between the hole detect interrupt and the main program were found to be updated without blocking that interrupt. No field reports are attributed to these, but each has a definite consequence on a production machine: a hole position or a die position wrong by a large amount, a hole seen by the interrupt but never reported, motor feedback counts on a SERCOS or EtherCAT machine counted twice or dropped, and an Open Loop target tested against a wrong position. All of them depend on a monitored input changing state at a particular moment, so they are intermittent and rare.

CAUSE

Two unrelated faults.

The Die Accelerator Test fault is that the encoder read used for an event such as a hole edge was also advancing the shared encoder data that the periodic one millisecond velocity and loop calculations depend on. Real encoder hardware, and a SERCOS or EtherCAT drive, hold a position between reads, so an extra read only splits the same movement into smaller pieces and nothing is gained or lost. The Die Accelerator Test holds no position; it generates its counts as it is read. Every edge on any monitored input therefore injected extra travel into whichever sample contained it, and the velocity filter reported that as a spike.

The second fault is that, on the V4 hardware, the shared values above are either thirty two bits wide, and so are written in two halves, or are flags packed into a single word that both the interrupt and the main program modify. An input edge arriving part way through one of those updates leaves a position built from half of the old value and half of the new, or overwrites the interrupt's own record that a hole has been seen, which is how a hole can be missed with its position already captured but never reported.

Contributing to the second fault, the routines used to block and restore interrupts, on the V4 hardwarte, did not put the previous state back when they finished. They simply enabled everything. A routine that had blocked interrupts could therefore be unblocked by any other routine nested inside it, and a handler could unblock itself part way through its own work.

CHANGE

Encoder event reads and periodic reads are now separate operations with separate entry points. An event read reports the count at that instant without disturbing anything the periodic sample depends on, and it does not advance a simulated encoder at all, since event accuracy during a Die Accelerator Test is not a requirement.

Blocking and restoring interrupts, on the V4 hardware, now counts how many times blocking has been requested and restores the exact state that was in force before the first request. Nested use is safe, and a handler can no longer unblock itself. This is the same behaviour the operating system already provides on the version five controller, so shared code now behaves identically on both.

Every shared value the hole detect interrupt can reach is now updated with interrupts blocked. A hole position, a die position, a motor feedback count or a hole detected flag can no longer be split in half or lost.